3000N specification OA Floor of steel panel. Standard type for general office.
Installation Location
It adopted to floor finishing height H50~300mm. The system is compounded with steel composite panel filled with lightweight inorganic material or hollow all steel panel, and aseismic supporting leg (DP leg) which is available to adjust height and has panel lock function.
Lock ring, to connect floor panel and supporting leg, can easily detach with specialized jig. The steel panel is good accuracy, so that there is no problem if it does not go back to previous location after changing layout. And also, can fix the partition directly to the panel.
2 sides of all steel floor panel have cable outlet ports are equivalent to φ12mm (semicircle), so that can pull out cable the way you want. And also, can install facility equipment as facing opening parts of opening panel (options) each other or changing to inner plug socket panel (option).
There are some items to comfort office space such as the floor air conditioning panel, panel with heater, etc.
The whisker is a conductive crystal generated by electro galvanizing, it is said to have a negative influence on computers. IB Floor 3000N Specification is not used electro galvanizing generates whisker.
The greatest feature of filling panel is that can obtain outstanding walking feeling by it filled with lightweight inorganic material. Filling panel is recommended at location which is a lot of traffic. Hollow panel has superior recyclability because of it made from steel single material. And also, it is lighter weight about 10kg/m² compare to filling panel, so that reduce load to building.
Steel Composite Panel Filling with Lightweight Inorganic Material
500×500×23(mm)
H50(mm)
About 7.8kg/ each
Steel Composite Panel Filling with Lightweight Inorganic Material(Standard Panel)
*Opening panel and IB opening cover are options.
500×500×28(mm)
H60〜300(mm)
About 7.6kg/ each
Hollow All Steel Panel (ECO Mark Certified Product)
500×500×23(mm)
H50〜300(mm)
About 5.0kg/ each
Supporting leg is aseismic type that height adjustment available and having panel lock function.
DP Leg
For AF Panel
DP Leg
For AZ3000/ AN3000 Panel
DP Leg
For AZ3000/ AN3000 Panel
Panel Construction Method
Column Separation Type
Panel・Column Connection Type (Aseismic Type)
Model No. | AF-DP | AZ3000-DP | AN3000-DP |
---|---|---|---|
System Weight(kg/m²) | About 32.2 | About 31.3~33.8 | About 20.9~23.4 |
Weakest Part Concentration Load(Pressurized Plateφ50) | 3000N (About 300kgf) Deflection within 5.0mm Residual Deformation within 3.0mm |
||
Aseismatic Performance | JIS A 1450 Vibration Testing, Mounted Load 350kg/m², Pass 1.0G |
AF Panel/ Hot dip galvanized steel sheet (filled lightweight inorganic material)
AZ3000 Panel/ Hot dip galvanized steel sheet (filled lightweight inorganic material)
AN3000 Panel/ Hot dip galvanized steel sheet (hollow specification)
Corresponding Floor Height H | 50 |
---|---|
Adjustable Range | +16 -0 |
Wiring Space h | 20 |
*Corresponding floor height H dimensions includes carpet tile thickness 7mm.
Corresponding Floor Height | 60 | 70 | 80 | 100 | 120 | 150 | 200 | 250 | 300 |
---|---|---|---|---|---|---|---|---|---|
Adjustable Range | +14 -2 |
±8 | +20 -8 |
±15 | |||||
Wiring Space | 25 | 35 | 45 | 65 | 85 | 115 | 165 | 215 | 265 |
*Corresponding floor height H dimensions includes carpet tile thickness 7mm.
*Please contact our sales department about more than H=310.
Corresponding Floor Height H | 50 | 60 | 70 | 80 | 100 | 120 | 150 | 200 | 250 | 300 |
---|---|---|---|---|---|---|---|---|---|---|
Adjustable Range | +16 -0 |
+14 -2 |
±8 | +20 -8 |
±15 | |||||
Wiring Space h | 20 | 30 | 40 | 50 | 70 | 90 | 120 | 170 | 220 | 270 |
*Corresponding floor height H dimensions includes carpet tile thickness 7mm.
*Please contact our sales department about more than H=310.
Opening panel of AZ3000-DP and IB opening cover are options. Please choose as required.
This dedicated panel sends conditioning air to the underfloor of OA floor and blows into the indoor from panel opening for the air conditioning residence area efficiently. (made-to-order)
Schematic Drawing
Conditioning air sent from the air conditioner to the underfloor chamber blows into the residence area through the air conditioning panel and air conditions efficiently. After that, it goes back to the air conditioner through the ceiling chamber from the suction port installed on the ceiling.
Pressure type panel blows conditioning air by air conditioner pressure from hollow perforated floor panel. The feature is less draft feeling. And also, can use for the ventilator of underfloor tends to stay moisture in.
*Please ask carpet tile with permeability separately for finishing material.
*The standard cover is steel closing plate.
Panel Size | 500×500×23.0 (only Panel) | ||
Material and Surface Processing | Hot Dip Galvanized Steel Sheet | ||
Panel Weight | About 5.5kg | ||
Opening Rate (/ each) | 6% | ||
Corresponding Floor Height | H70~300mm | ||
Finishing Material | Permeable Carpet Tile (by Others) | ||
Corresponding OA Floor | AF・AN・AZ Series | ||
Load Resistance Performance | 3000N Specification |